Alerting

Functional description

As part of the HOOC alert solution, the alerting (or alarming) service enables you to define specific alarm rules for your system monitoring and the notification in case of a system failure. If you wish, you can also combine different other HOOC services with the alerting service. For example: You might want to be alerted if the values sent from the Secure Remote Control Service (SERC) are too high/low. Or you want to be informed when the Secure Remote Access (SERA) detects an (un-)authorized person accessing your system.

With the alerting service, you can also combine different alarm rules and conditions (e.g. when heating on, but temperature too low –> send alarm). You also have the possibility to test those alarm rules and conditions beforehand (see next point).

Please note that the alarm notification channels (voice message, push, SMS or e-mail) have to be configured in the HOOC Notification Center (see next chapter).

Alarm rules configuration

The alarming service can be configured under the specific Site(s), then Services –> Alerting.

services-alerting

As mentioned above, you can test every alarm rule beforehand. The test result will then be shown in the Last status column. If an alarm value has been defined in the settings, it is also displayed in parentheses (in so far as alert value > 1).

  • In order to manually update the alarm rule, click on the icon.
  • In order to test the alarm rule (with redirection to the Notification Center), click on the icon.

Depending on the configuration of the rule, the following operations are available:

Operations Description
Pause the process
Start the process
Send an alarm message via the Notification Center to the notification channel
Acknowledge the alarm

The following actions are also available:

Actions Description
Edit the alarm rule
Copy the alarm rule
Show the alarm log / alarm history
Remove the alarm rule

Create alarm rules

You can add a new alarm rule by clicking on the icon. The following settings can be made:

General

services-alerting-rule-tab0

Property Description
Rule name Specify the alarm rule (the name entered here will also be shown as such in the HOOC apps).
Multilingual … Add the rule name in the corresponding language (optional). The name entered here will be, depending on the language settings, shown as such in the HOOC apps.
Category Categorize the alarm rule (e.g. information, warning, alert etc.)
Labels Labels for grouping alarm rules can be defined. The Notification Centers provide filtering options based on the alarm rule labels.
Rule active Check this field if you want to activate the alarm rule (otherwise the rule is not in force).

If the option Report if the result of the rule changes … from the general settings is activated, the notification will be sent with the status OK.

Messages

services-alerting-rule-tab1

Each alarm message can be assigned a different status (e.g. “on alert”, “on acknowledgement” and “on recovery”).

Property Description
Title Enter the title of the message
Message Enter the message text
Multilingual … Enter the translated terms, which, depending on the language settings, will then be used for the alarm message (optional)

You can also use placeholders or wildcards. These will be replaced by the corresponding values once the message is created.

Example Description
{{0}} Stands for the evaluated alert value
{{1}}, {{2}}, {{3}} Stands for the respective value of the alarm condition (see next point)
{{ACKED_BY}} Stands for the name of the person who has acknowledged the alarm
{{ESCALATION_LEVEL}} Represents the current escalation levels

Conditions

services-alerting-rule-tab2

In order to create a rule, you have to specify at least one condition. However, you can also combine several conditions together.

  • To add a new condition, click on .
  • To delete the condition, click on .
  • To move conditions, use “drag and drop”.

Logical operators

The first condition always starts with the operator WHEN. If you opt for multiple conditions, there are several logical operators you can use:

Logical operator Description
AND AND operator
NAND NOT-AND operator
NOR NOT-OR operator
OR OR operator
XNOR EXCLUSIVE-NOT-OR operator
XOR EXCLUSIVE-OR logic operator

Please note that the conditions are to be combined one after the other. Condition_01 is to be combined with Condition_02. This result is then combined with Condition_03 and so on.

Using your HOOC gateway as data source (Secure Remote Access)

If you want to use the HOOC gateway respectively the Secure Remote Access as a data source for your alerting, you have different options available. So you can e.g. use the connection status (for a specific time period) as a condition for an alarm rule or the number active of user sessions.

Using a data point as data source (Secure Remote Control)

If you would like to use the data source data point respectively the Secure Remote Control for your alerting, you can select the specific data point by drop-down.

Please note that in case the data point name in the Secure Remote Control service is changed, this setting will not automatically be transferred. This can lead to an incorrect result of the corresponding rule.

The conditions terms are described as follows:

Terms Description
Mean value Stands for the sum of all measured values during a specific time period divided by the number of measured values of this period (arithmetic mean)
Median value Represents the middle value in distribution when the values are arranged in ascending or descending order.
Value validity Stands for the validity of the measured values. Important: If the data point value of an event-driven protocol (e.g. KNX) is marked as invalid for the entire period (Last known value), the value 0 (out of order) is assigned.
Change of value Checking a change in value over time

After having selected the query definitions of the data point, you can enter the operator and the corresponding limit values.

For non-event-driven protocols (e.g. Modbus TCP): Please note that if no values of the data point are available, the value null is assigned. For event-driven protocols (e.g. KNX): You can check the validity of the data point with the query definition value validity.

Using your KNX device as data source (Secure Remote Control)

In order to monitor the connection to your KNX gateway/router or to check the bus load, you want to use the data source KNX device.

Using your LoRa device as data source (Secure Remote Control)

In order to monitor the connection to a specific LoRa device, you want to use the data source LoRa device. Important: If no data could be received from the LoRa device during the predefined time interval, the connection is shown as disconnected.

Relational operators

From the table below, you can see the possible relational (comparison) operators.

Description Operation Information
equal applies if (value == field0)
greater applies if (value > field0)
smaller applies if (value < field0)
within applies if ((value >= field0) && (value <= field1))
outside applies if ((value < field0) && (value > field1))
null applies if (value == null) applies if there is no value available
only bits applies if ((value > 0) && ((value & bitmask) == value)) If the value is not integer, the result will be FALSE
one bit applies if ((value & bitmask) > 0) If the value is not integer, the result will be FALSE
all bits applies if ((value & bitmask) == bitmask) If the value is not integer, the result will be FALSE
no bit Applies if ((value & bitmask) == 0) If the value is not integer, the result will be FALSE

Testing the conditions

You can test the conditions of every alarm rule, by clicking on “Test conditions”. The rule will then be tested, without any messages being sent. After the testing, the following results appear:

  • The value of the data source is displayed in the tooltip
  • Result “condition TRUE
  • Result “condition FALSE

The result of the rule is displayed to the left of the “Test conditions” button.

Alarm value

services-alerting-rule-tab3

The alarm value is an optional setting. If the alarm value changes, the alarm rule is re-evaluated. The following must be considered:

  • The value range of the associated data point is interpreted as UINT (value between 0 and 65536).
  • The alarm value 0 sets the alarm rule to the “OK” state regardless of the condition.
  • The alarm value is stored in the alarm events log

Escalation

services-alerting-rule-tab4

You can assign your escalation rules in the configuration tab Escalation. Escalation rules define the escalation process in case of a technical problem as well as the interval in which the alarm messages will be sent (until the alert will have been acknowledged).

In the dropdown field Selection of escalation rule choose an already defined escalation rule in order to assign it to the alarm rule or choose to enter an individual escalation rule.

Enter an individual escalation rule as follow:

Property Description
Start escalation level Time between the start of the previous escalation level and the start of the current one.
Message Interval Select the time interval, in which you want the alarm message to be sent during the current escalation level

You can acknowledge an event or alarm, by clicking on the icon.

Please note that in case of an event (according to your predefined conditions), the escalation level 0 comes automatically into effect. In case you have predefined specific escalation rules for that event, automatically the escalation level 1 comes into effect. “Automatically” here means; as soon as the first predefined condition occurs.

Collaboration

services-alerting-rule-tab5

You can choose your individual settings for chat and messages in the Collaboration tab. If you want your recipients to receive alarm notifications with the HOOC CollabApp, you have to activate the Use in Collaboration Service option.

For each alarm rule, you can define specific texts which you want your recipients to receive over the HOOC CollapApp.

Escalation rules configuration

services-alerting

Escalation rules define the escalation process in case of a technical problem as well as the interval in which the alarm messages will be sent (until the alert will have been acknowledged). It is possible to record a maximum of 8 escalation levels.

An overview of the configuration is displayed for each of the defined escalation rules and the following actions are available:

Actions Description
Edit the escalation rule
Copy the escalation rule
Remove the escalation rule

Create escalation rules

You can add a new escalation rule by clicking on the icon. The following settings can be made:

services-alerting

Property Description
Rule name Specify the escalation rule name (the name entered here will also be shown as such in the escalation tab of alarm rules apps).
Option Restart escalation after reaching the last level Check this box, if you want that the message(s) to be sent once again to the recipients of the first escalation level, in case no one from the other escalation levels has yet acknowledged the alarm.
Time delay restart escalation Select the time period, in which you want the whole escalation process to be restarted (back to escalation level 1) after the last escalation level has been reached (and has not responded/acknowledged).
Start escalation level Time between the start of the previous escalation level and the start of the current one.
Message Interval Select the time interval, in which you want the alarm message to be sent during the current escalation level

Use in the HOOC apps

The functionalities of the different communication channels, the settings for receiving notifications and the configuration of the Message Center can all be made in the HOOC apps. Furthermore, the following settings can be made:

  • Alarms can be acknowledged in the Alerting menu by swiping the corresponding item to the right.
  • The settings for the Notification channels options can be made under the specific Site(s) in the More menu.